Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM05514
Parcel: 134244310

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05514
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2015 MARTIN BROWN FIRE REVIEW Approved
08/28/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN REVIEW COMMENTS
Date: 8-31-15
Activity: T15CM05514
Address: 6343 E. 22nd St 141
Applicant: Randy Haislet

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

Sheet CS:
1. Provide sheet A4.0 for review as indicated on the sheet index, 107.2.

Sheet A2.0:
2. Provide a clear path of accessible egress through door 6 located between the appliance and clearance areas. An existing post is shown obstructing this path, 1005.4.

Sheet A3.1:
3. Include the capacity of the 400 watt halogen light (indicated near the door in the northeast corner) on the electrical design and outdoor lighting calculations, OLC 3.1.2.

Sheet A5.1:
4. Provide vertical grab bars as required by ANSI A117.1, 604.5.1.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
08/31/2015 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/31/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 604.9, IPC 2012.
08/31/2015 ROBERT SHERRY WATER REVIEW Completed
08/31/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.