Permit Number: T15CM05468
Parcel: 12704293A

Address:
4901 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM05468
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change Please break up the occupant load per room. Rooms or Spaces in I-4 Occupancies that have an occupant load of 10 or more require 2 exits.

Door 121A obstructs the egress path per 1005.7.1.

Sheet A2.0 shows key notes 18, what is the hardware as the doors noted with key notes are not on Door Schedule? What is the fire rating if it is being used for rated stairway?
10/08/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change Pending Fire comments associated with egress.
10/12/2015 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/12/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/12/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/12/2015 ROBERT SHERRY WATER REVIEW Completed