Permit Number: T15CM05468
Parcel: 12704293A

Address:
4901 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05468
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change I would like current building official to determine occupancy classification. I-4 adult daycare or B occupancy.
08/25/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN REVIEW COMMENTS
Date: 8-26-15
Activity: T15CM05468
Address: 4901 E. 5th St
Applicant: Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

Sheet A1.0
1. Information posted on the tenant's website indicates the primary clientele are 'developmentally disabled' to include cerebral palsy and cognitive disorders. Services rendered to persons suffering from these debilitating conditions may not be capable of self preservation yet the letter of intent indicates that all occupants are capable of self preservation. If this facility does not include clients that are developmentally disabled then please specify which facility operated by this organization provides such services.
2. Please include on the code analysis the proposed occupant load, 1004.1.
3. Provide a means of egress plan that indicates the distance of common path of egress and maximum travel distances, 1014.3, 1016.1.
4. Please indicate the location of the accessible means of egress on the site plan, 3411.7.
5. Three (3) accessible parking spaces are required for the quantity of parking spaces shown, 1106.1

Sheet A2.0
6. Define the door type and hardware labeled 112A located between the lobby and the adjoining activity room.
7. Two (2) exit access stairways are required, 1021.2. Note:
-Exit access stairways must lead directly to the exterior of the building or shall be extended to the exterior of the building with an exit passageway, 1022.1.
-At least one exit access stairway must be an interior exit stairway, 1009.2.1.
-Exterior exit stairways must meet the open requirements of 1026.3.
8. Please indicate the location and method of 1 hour fire-rated construction for the interior exit stairway enclosure, 1022.2.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
08/26/2015 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
09/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2015 ROBERT SHERRY WATER REVIEW Reqs Change Tucson Water limits 1-1/2" water meters to maximum demand of 75-GPM. Using the IPC fixture units and demand curve, as required by Tucson Water, the demand will be approximately 89 GPM instead of the 72 GPM demand obtained using the UPC fixture units and demand curve. Provide a letter from Tucson Water allowing a 1-1/2" water meter to be used for this demand. Reference: Section 107.2.1, IBC 2012.
09/08/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. the clothes washer, P11). Reference: Section 604.9, IPC 2012.
2. Verify the point of connection to the public sewer. If the connection is south of the building instead of to the north, provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
3. Verify the size of the existing section of gas pipe located between (E) AC-7 and new AC-2. Using Table 402.4(2), IFGC 2012, a load of 180 CFH at 175 feet would require a 1-1/4" pipe instead of the existing 1" pipe.
09/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the location of the return grilles for conference rooms A and B; are they discharging into the return air plenum?
2. Clarify how the return air from the first floor rooms enters into the return air plenum without using the egress corridor as a duct. Reference: Section 601.2, IMC 2012.
3. The NFRC web site does not recognize the CPD # submitted on the envelope compliance certificate (SOL-A-16-00099-00001). Provide documentation for the specified window.