Permit Review Detail
Review Status: Completed
Review Details: REVISION - WALK THRU
Permit Number - T15CM05445
Review Name: REVISION - WALK THRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/12/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following plan review comments. #1. Total load ( amps )on the B Phase of Panel WPD exceeds the Rating of the panel. #2. Update ( cloud in ) all Panel schedules with revised circuiting. #3. Provide a Panel schedule and Panel designation for the revised lighting. Ref: IBC sec. 107.2.1, NEC art. 110.3, 408. |
| 11/16/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PLEASE PROVIDE A LETTER INDICATING CHANGES THAT HAVE BEEN MADE FOR THIS REVIEW. IN ADDITION, PLEASE PROVIDE THE ORIGINAL DRAWINGS THAT HAVE BEEN CHANGED. 2. SHEET A-201; SECOND FLOOR PLAN: THE NORTH WALL OF THE RESTROOMS INDICATES A CHANGE HAS BEEN MADE, BUT THE SHEET A-602 HAS NOT BEEN INCLUDED IN THIS SET. PLEASE PROVIDE THAT SHEET INDICATING THE CHANGES IN THE NORTH WALL. 3. |
| 11/17/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |