Permit Number: T15CM05445
Parcel: 12701003K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05445
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/21/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Double check valves (ASSE 1015) are testable but do not have an intermediate atmospheric vent like the ASSE 1022-listed dual checks. Section 608.1, IPC 2012 requires the choice of backflow protector to "conform to Table 608.1, [IPC 2012] except when specifically stated in Sections 608.2 through 608.16.10." Section 608.16.10 specifically requires the use of an ASSE-listed backflow preventer to be used for coffee machines and non-carbonated beverages. [Initial comment: Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Sections 608.16.1 and 608.16.10, IPC 2012.]
2. The vent for the floor drain is still shown as running horizontally below the slab on sheet -P101. [Initial comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. the showers and floor drain). Reference: Section 905.4, IPC 2012.]
10/21/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Based on the floor plan shown on sheet F-201, rooms 201 and 226 appear to be telephone/data entry spaces which have a higher occupancy rate than an office. Clarify how these rooms are to be used. Reference: Section 107.2.1, IBC 2012. [Initial comment: The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements or the furniture layout. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2012 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2012.]