Permit Number: T15CM05382
Parcel: 10511061R

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM05382
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2015 EGALLET1 BUILDING-COMMERCIAL REVIEW Needs Review
11/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains shall be terminated at an approved disposal location (i.e. spilling to the roof in not acceptable). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
2. Show that the rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
11/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/24/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please clarify in detail changes on plan sheet E3 Lighting, adding luminaires or just changing the lighting arrangment.
Also clarify changes to the One Line Diagram, and update all panel schedules.
Ref : IBC 107.2.1, NEC 408.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2015 EGALLET1 OUT TO CUSTOMER Completed