Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM05382
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/24/2015 | EGALLET1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
11/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate drains shall be terminated at an approved disposal location (i.e. spilling to the roof in not acceptable). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 2. Show that the rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. |
11/24/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
11/24/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please clarify in detail changes on plan sheet E3 Lighting, adding luminaires or just changing the lighting arrangment. Also clarify changes to the One Line Diagram, and update all panel schedules. Ref : IBC 107.2.1, NEC 408. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/24/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |