09/09/2015 MARTIN BROWN FIRE REVIEW Approved
09/22/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
09/22/2015 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
2. Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012.
09/24/2015 ROBERT SHERRY WATER REVIEW Completed
09/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.
09/28/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide:
#1. Plan sheet E-4.
(a). Include AIC rating on the panel schedules and the available fault current at the panel supply side feeders.
(b). Main circuit breakers are required for both panels 'L' and 'P' as required per NEC art. 408.36B.
(c). Overcurrent protection ( Fuses ) for the 75kva primary transformer protection seem to be oversized. NEC art. 450.3B.
(d). Provide complete compliance with the IECC for interior lighting.
Ref: IBC sec.107.2.1, NEC, IECC