Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM05381
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate drains shall be terminated at an approved disposal location (i.e. spilling to the roof in not acceptable). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 2. Show that the rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. |
| 11/24/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please clarify changes to the one line diagram. And RTU #1 is not shown on the panel schedules. Ref: 107.2.1 |
| 11/30/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 12/04/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |