Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM05381
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | No changes made to P-1: 1. The Plumbing Fixture and Equipment Schedule includes a water cooler; is it part of this activity? Reference: Section 107.2.1, IBC 2012. 2. Clarify the routing of the vent for the combination waste and vent system (for the mop sink and floor drain); it appears to be rising through the middle of the room. Reference: Section 107.2.1, IBC 2012. 3. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 4. Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012. 5. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012. |
| 10/14/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Comments not addressed per the last electrical plan review. |
| 11/05/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Previous Comment: 1. Please provide an accessible path between the front and back areas of the store near the side exit door. A minimum 36 inch clear width is required, ANSI A117.1, 403.5. Note: The configuration of walls near the side door do not appear to provide the minimum required path of travel through this area. Please feel free to contact me with any questions. Clayton Trevillyan, CBO City of Tucson 520.837.4913 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/10/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 11/10/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 11/10/2015 | AROMERO4 | REJECT SHELF | Completed |