Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05381
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/21/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | BUILDING PLAN REVIEW COMMENTS Date: 9-22-15 Activity: T15CM05381 Address: 4500 N Oracle #233 Applicant: Metro TED This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval. 1. Please provide an accessible path between the front and back areas of the store near the side exit door. A minimum 36 inch clear width is required, ANSI A117.1, 403.5. 2. Provide a minimum 36" clear width through the stock room area between shelving units, A117.1, 403.5. If you have any questions please contact: Clayton Trevillyan, CBO 520.837.4913 Clayton.Trevillyan@tucsonaz.gov |
| 09/22/2015 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/24/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The Plumbing Fixture and Equipment Schedule includes a water cooler; is it part of this activity? Reference: Section 107.2.1, IBC 2012. 2. Clarify the routing of the vent for the combination waste and vent system (for the mop sink and floor drain); it appears to be rising through the middle of the room. Reference: Section 107.2.1, IBC 2012. 3. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 4. Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012. 5. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012. |
| 09/24/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/28/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1. Please provide complete compliance with the IECC for interior lighting. #2. Include the AIC rating on the panel schedule. |