Permit Number: T15CM05365
Parcel: 124031700

Address:
1832 E 6TH ST

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T15CM05365
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2015 KEN BROUILLETTE FIRE REVIEW Approved
08/17/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN REVIEW COMMENTS
Date: 8-18-15
Activity: T15CM05365
Address: 1832 E. 6TH St
Applicant: Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

1. Please provide structural calculations for tower installation that include the minimum size and location of the temporary concrete pier locations from the base of the tower they are supporting, 107.1.
2. Specify the proposed location of the temporary concrete piers (shaded limits will suffice). Minimum distances from the tower must be maintained for structural stability and maximum limits will be based on pedestrian travel, electric utility lines and/or property lines, 3108.2.
3. Indicate the location of electric service lines to the existing building, 107.2.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
08/19/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide for a second ground rod ( 2 ) total, to be installed as a supplemental rod as required per NEC art. 250.53A2, 3. Or a single ground rod is acceptable per the exception, provided a ground resistance test is performed and submitted to the AHJ and the ground resistance to earth is 25 ohms or less.
Ref: NEC art. 250.
08/20/2015 FRODRIG2 COMMUNICATIONS REVIEW Approved APPROVAL LETTER IN RECORDS.
08/20/2015 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2015 KROBLES1 OUT TO CUSTOMER Completed