Permit Number: T15CM05260
Parcel: 110120990

Address:
2650 N WYATT DR

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM05260
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/31/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/31/2015 JASON GREEN ENGINEERING REVIEW Approved
07/31/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
09/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide: #1. Include voltages, amperage rating for all electrical equipment on the one line diagrams.
#2. Clarify if the existing generator is to remain or to be removed .
#3. Indicate or verify if the new generator is optional standby or Emergency.
#4. Provide for a selective coordination analysis.
#5, Provide GFI protection for feeders as required per 230.95 and 517.17 NEC.
#6. Provide complete compliance with the Tucson Outdoor Lighting Code for the exterior lighting.
Ref: IBC sec. 107.2.1, NEC art. 230, 517.
09/22/2015 MARTIN BROWN FIRE REVIEW Reqs Change 1. Provide specs on generator.
2. Correct NFPA 110 reference year
3. Is this as Level I generator and if it is indicate how it meets NFPA 110 requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2015 AROMERO4 OUT TO CUSTOMER Completed