Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/31/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/31/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
07/31/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
07/31/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
09/22/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide: #1. Include voltages, amperage rating for all electrical equipment on the one line diagrams. #2. Clarify if the existing generator is to remain or to be removed . #3. Indicate or verify if the new generator is optional standby or Emergency. #4. Provide for a selective coordination analysis. #5, Provide GFI protection for feeders as required per 230.95 and 517.17 NEC. #6. Provide complete compliance with the Tucson Outdoor Lighting Code for the exterior lighting. Ref: IBC sec. 107.2.1, NEC art. 230, 517. |
09/22/2015 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1. Provide specs on generator. 2. Correct NFPA 110 reference year 3. Is this as Level I generator and if it is indicate how it meets NFPA 110 requirements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/20/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |