Permit Number: T15CM05250
Parcel: 13355231B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM05250
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
08/31/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan Sheet PV 1, note 2 of the riser diagram notes, allows for a bus tap option at the Utility interconnection in the main distribution panel. Please provide a detail or drawing to accomodate this option. Also include the fused disconnect switch location ( should be as close as possible to the Main Switchboard ). Provide for a third party NRTL field inspection , and approval to maintain the Listing of the equipment.
Ref: IBC sec.107.2.1. NEC art. 110, 230.66, 690, 705.
09/01/2015 KEN BROUILLETTE FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2015 AROMERO4 OUT TO CUSTOMER Completed
09/10/2015 FERNE RODRIGUEZ REJECT SHELF Completed