Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM05236
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The City of Tucson has adopted the 2012 IMC as the approved method for calculating ventilation requirements; provide calculations demonstrating adequate ventilation using the current code. If you wish to provide a ventilation rate greater than the minimum required, show how the HVAC controls are capable of reducing the outside air to the minimum flow rates required by Chapter 4, IMC 2012. Reference: Section C403.2.5, IECC 2012 and Sections 403.2, 403.3, and 403.3.2.3, IMC 2012. [Initial comment: Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.] |
| 09/16/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Install the proposed vacuum relief valve for the water heaters per the manufacturer's listing information, i.e. with no valves located between the vacuum relief valve and the water heater. Reference: Section 303.2, IPC 2012. [Initial comment: Provide a full-open valve for the water supply pipe to the water heater. Reference: Section 606.1(8), IPC 2012.] 2. Provide a cleanout for the horizontal drain located downstream of the mop sink fixture drain. [Initial comment: Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012.] |