Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM05236
Parcel: 13321074A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05236
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2015 MARTIN BROWN FIRE REVIEW Approved
08/14/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
08/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.
08/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a full-open valve for the water supply pipe to the water heater. Reference: Section 606.1(8), IPC 2012.
2. Based on the shell drawings, a 3" horizontal branch drain was provided for the future installation of a mop basin. Verify the size of the existing branch and its location (it is shown on the shell drawings as being separate from the restroom drains). A 4" drain for the mop basin cannot be connected to the existing 3" branch drain. Reference: Section 704.2, IPC 2012.
3. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012.
08/20/2015 ROBERT SHERRY WATER REVIEW Completed
08/24/2015 STEVE SHIELDS ZONING REVIEW Approved
08/25/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved