Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05236
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/14/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 08/20/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. |
| 08/20/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a full-open valve for the water supply pipe to the water heater. Reference: Section 606.1(8), IPC 2012. 2. Based on the shell drawings, a 3" horizontal branch drain was provided for the future installation of a mop basin. Verify the size of the existing branch and its location (it is shown on the shell drawings as being separate from the restroom drains). A 4" drain for the mop basin cannot be connected to the existing 3" branch drain. Reference: Section 704.2, IPC 2012. 3. Provide cleanouts for all horizontal drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012. |
| 08/20/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/24/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/25/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |