Permit Number: T15CM05198
Parcel: 12213055F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05198
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2015 DAVID RIVERA ZONING REVIEW Approved
08/05/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The new water heater is not shown on the architectural drawings. Provide structural support details for the water heater.
08/05/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/05/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the listing and installation instructions for the boil-out unit. Provide the listing information for the vent-a-kiln exhaust fan/hood assembly. Reference: Section 301.7, IMC 2012. [Initial comment: Provide listing and installation instructions for the kiln exhaust hood and the boil-out unit.]
08/06/2015 AROMERO4 FIRE REVIEW Needs Review