Permit Number: T15CM05184
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05184
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2015 MARTIN BROWN FIRE REVIEW Passed
08/13/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN REVIEW COMMENTS
Date: 8-14-15
Activity: T15CM05184
Address: 5870 E. Broadway #214
Applicant: Metro TED

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

Sheet A041:
1. Please clarify the egress door hardware set #2. Specified hardware type not found.

Sheet A090:
2. Correct code reference indicated. Should CBC 2013 be IBC 2012?

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
08/17/2015 ROBERT SHERRY WATER REVIEW Completed
08/17/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
2. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Section 607.1.2, IPC 2012.
3. Provide cleanouts sized per Section 708.7, IPC 2012.
08/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the HVAC unit controls have been provided with an automatic start capability. Reference: Section C403.2.4.3.3, IECC 2012.
2. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Verify the termination point of the roof drains. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
3. The City of Tucson has adopted the 2012 IMC as the approved method for calculating ventilation requirements.
4. Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.
08/21/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.
Also Please update the Registrant Expiration Date.