Permit Number: T15CM05171
Parcel: 119210240

Review Status: Completed

Review Details: WALK THRU - RES

Permit Number - T15CM05171
Review Name: WALK THRU - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change 1. Justify roof framing support for the roof-mounted equipment. It is not clear what the proposed 2x4 supports are connected to in order to provide sufficient load transfer.
2. Please specify the capacity of the electric service to supply the proposed 50 amp breaker. An electrical load calculation will be necessary if the service is less than 150 amp.