Permit Number: T15CM05144
Parcel: 106060180

Address:
1300 W PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05144
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/23/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The revised equipment list for the gas-fired appliances still indicates an energy content of 1100 BTU per cubic foot of natural gas. With 1,000 BTU per cubic foot, 1CFH of gas will provide 1,000 BTUH. [Initial comment: Clarify the connected loads or input ratings for each appliance. Southwest Gas provides natural gas with an energy content of approximately 1,000 BTU per cubic foot. Revise the pipe sizes as required and show the required size for each pipe section. Reference: Section 402.1, IFGC 2012.]
2. Provide a detail of the storage-type water heater installation, including the excess pressure/temperature relief, expansion tank, safety pan, and valves. [Initial comment: Provide a detail of the booster water heater installation, including the excess pressure/temperature relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.]
10/23/2015 ROBERT SHERRY WATER REVIEW Completed
10/30/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments, please include a written response.
#1. Subsequent or the second Electrical plan review shows additional electrical equipment and items not shown on the previous plans. New lumenaires, service equipment ( one line diagram ).
Please provide a complete electrical plan or plans as needed and as required per the City of Tucson Commercial Plan Submittal Requirements, to provide all the information and documents necessary to provide a complete electrical plan review. These requirements are outlined and can be downloaded off the City website, www.tucsonaz.gov/pdsd.
Ref: IBC sec 107.2.1