Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T15CM05123
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 07/29/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Michael St.Paul, Planning Technician PROJECT: T15CM05123 2190 East Benson Highway (132-19-015A) Cell Tower antennas TRANSMITTAL: July 29, 2015 COMMENTS: the following comments are relative to an application for a Special Exception relative to cell tower antenna modifications. Approval of the new special exception is required. Demonstrate compliance with the conditions of the special exception on the plans |
| 07/31/2015 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | Special Exception needs to be approved prior to approval of the CM permit. ENG will stamp the cell tower plan approved over the counter once ZON stamps it approve. |
| 08/04/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1.Please provide a complete single line diagram, including fault current, load calc's, all conduit , conductor sizes and types ,for the new 200 amp service, include all associated equipment, complete panel schedules. #2. Please include the existing generator interconnections to new equipment. Ref; Plan Sheet 'A2' IBC sec. 107.2.1, NEC art. 110, 230, 300, 250. |
| 08/14/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 08/21/2015 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | Approval letter sent to records. |
| 09/01/2015 | FRODRIG2 | PLANNING-CITY HALL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/11/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |