Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM05115
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Previous Comment: Sheet M3.00 2. Specify the proposed support and attachment for suspended mechanical equipment, 107.2. Note: Please justify the structural support of the suspended unit. Include information regarding the weight of the unit, number of threaded rods, and type of concrete anchors supporting the threaded rods along with structural capacity of existing floor system they are mounted to. |
| 08/28/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/08/2015 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |