Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/24/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | PROVIDE MANUFACTURER CUT SHEET FOR CONNECTION HARDWARE THAT ATTACHES PANELS TO STRUCTURE |
08/25/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following comments. #1. Provide conduit, conductor sizes , types, circuit and panel designations, wiring methods for the new canopy lighting. Include wiring between canopies. #2. Provide a directory, denoting all power sources on the premises at all locations required by NEC art. 690.54, 705.10 IBC sec. 107.2.1 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/28/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |