Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15CM05057
Parcel: 129020010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM05057
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The specified backflow (Watts 9D) is certified to ASSE 1012, not the required ASSE 1022. [Second comment: Beverage dispensers, such as coffee makers, require the use of a backflow preventer that is listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012.] [Initial comment: Appliances (e.g. beverage dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.]
11/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/20/2015 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review