Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM05011
Parcel: 12108054B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM05011
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
08/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the mechanical COMcheck for "alteration", not new comnstruction.
2. Provide the envelope COMcheck, include documentation for the glazing.
3. Provide for interlocking HP-3 with EF-4.
08/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1.Please provide a complete panel schedule for 'EMDP'
#2. One line diagram shows two panels designated as 'A'.
08/10/2015 KEN BROUILLETTE FIRE REVIEW Passed
08/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the water distribution calculations, using the stated alculation method (i.e. Section 6.5, UPC 2006)
2. Clarify the fixture tags used on the isometrics and the plumbing plans.
3. Verify the static lift used for the water pressue calculations.
4. Verify the size of the scheduled water service to the water closets.
08/10/2015 ROBERT SHERRY WATER REVIEW Completed
08/11/2015 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review
08/11/2015 KROBLES1 ENGINEERING REVIEW Needs Review
08/11/2015 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review