Permit Number: T15CM04882
Parcel: 11714346D

Address:
520 S MEYER AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM04882
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM04882
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity referenced at keynote #8/A3 and supported by keynote #10/S1, R301.1.

ELECTRICAL PLANS:

1. Small appliance circuits at the kitchen countertop receptacle outlets may also serve the breakfast room and dining room, but not other locations, E3703.2 and E4001.3.1 through E4001.4.5. Place the exterior receptacle on a circuit other than the small appliance or bathroom circuit.
2. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3901.7. These outlets require GFCI protection, E3902.3.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/14/2015 AROMERO4 OUT TO CUSTOMER Completed