Permit Number: T15CM04751
Parcel: 12108001B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM04751
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved; two floor sinks still have vents that run horizontally prior to rising 6" above the flood rim of the floor sinks. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally.] Reference: Section 905.4, IPC 2012.