Review Details: COMMERCIAL - TI

Permit Number - T15CM04711
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/10/2015 JASON GREEN ENGINEERING REVIEW Approved
07/10/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: BE AWARE THAT IF THE ASSEMBLY OR RETAIL OCCUPANCY TYPES ARE USED, A FAMILY OR ASSISTED USE TOILET MAY BE REQUIRED PER THE IBC SECTION 1109.2.1. THIS WILL BE REVIEWED FOR THE TENANT IMPROVEMENT IN THIS SPACE.
2. SHEET S1.0: PLEASE VERIFY ON THE DRAWINGS THE NEW MECHANICAL LOADS ADDED FOR THIS PROJECT DO NOT EXCEED THE ALLOWABLE LOAD CAPACITY OF THE EXISTING STRUCTURE.
3. GENERAL: THIS SPACE MAY NOT BE USED UNTIL A CERTIFICATE OF OCCUPANCY IS ACQUIRED.
4. GENERAL: PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS.
07/10/2015 ROBERT SHERRY WATER REVIEW Completed
07/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
07/13/2015 KEN BROUILLETTE FIRE REVIEW Approved
07/21/2015 KROBLES1 ZONING REVIEW Needs Review