Permit Number: T15CM04704
Parcel: 13423411A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM04704
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2015 STEVE SHIELDS ZONING REVIEW Reqs Change Development package required due to site changes.
07/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
07/10/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/10/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size and serial number of the water meter serving this store along with the size of the associated reduced pressure zone backflow prevention assembly.
07/10/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/10/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). In addition, clarify the date the drawing was sealed.
3. Terminate the sump pump discharge per Section 712.3.5, IPC 2012.
07/10/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/13/2015 KEN BROUILLETTE FIRE REVIEW Approved
07/14/2015 JASON GREEN ENGINEERING REVIEW Needs Review