Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T15CM04659
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Michael St.Paul, Planning Technician PROJECT: T15CM04659 2316 East Fifth Street Addition to SFR TRANSMITTAL: July 8, 2015 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The height of the wall of the proposed addition is thirteen (13) feet, eight (8) inches. The required setback for the addition to the east property line is nine (9) feet, one (1) inch. The proposed setback is four (4) feet. |
| 07/08/2015 | MICHAEL ST. PAUL | NPPO | REVIEW | Passed | |
| 09/11/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 09/11/2015 | EGALLET1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change |