Permit Number: T15CM04658
Parcel: 105102680

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM04658
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2015 DAVID RIVERA ZONING REVIEW Approved
07/09/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The HVAC design appears to utilize a return air plenum. Verify that no combustible materials are located within the plenum. Reference: Section 602.2.1, IMC 2012.
2. Provide calculations to show that adequte ventilation is being provided. Reference: section 403.3, IMC 2012.
07/09/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the IECC for the interior lighting. Also verify expiration date for the registrant of record.
07/09/2015 JASON GREEN ENGINEERING REVIEW Approved
07/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/09/2015 ROBERT SHERRY WATER REVIEW Completed
07/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Keynote 6 for the architectural floor plan calls for a "plumbed water cooler". If this is new, show how it is to be plumbed and where the accessible cup dispenser will be mounted. Reference: Section 107.2.1, IBC 2012.
07/09/2015 KEN BROUILLETTE FIRE REVIEW Approved
07/09/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed