Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM04658
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/09/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 07/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The HVAC design appears to utilize a return air plenum. Verify that no combustible materials are located within the plenum. Reference: Section 602.2.1, IMC 2012. 2. Provide calculations to show that adequte ventilation is being provided. Reference: section 403.3, IMC 2012. |
| 07/09/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with the IECC for the interior lighting. Also verify expiration date for the registrant of record. |
| 07/09/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/09/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Keynote 6 for the architectural floor plan calls for a "plumbed water cooler". If this is new, show how it is to be plumbed and where the accessible cup dispenser will be mounted. Reference: Section 107.2.1, IBC 2012. |
| 07/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 07/09/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |