Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T15CM04649
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/11/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T15CM04649 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. FOUNDATION PLANS: 1. Show the minimum 12" footing depth below the undisturbed ground surface for the porch footer, R403.1. FLOOR PLANS: 1. Identify the materials at the window opening next to the refrigerator, R106.1.1. STRUCTURAL PLANS: 1. The integrity of the proposed non-prescriptive block wall structure requires verification, R301.1.3. Provide the manufacturer's engineered installation requirements for the 10" E.F. block. SECTIONS - DETAILS: 1. Clarify the placement of ceiling/roof insulation for determining the need for roof ventilation, R806. 2. Show a roof ventilation plan with a minimum 1" air space between the insulation and roof sheathing, R806. And show attic vent openings effectively sized for the attic area per R806.2. Or provide condensation control with an air-impermeable rigid insulation material tight to the roof sheathing with a minimum R-5 value, R806.5. The total insulation value may be achieved with foam (spray/board) and batt layers. 3. Notate and specify a complete porch roofing system: Roof sheathing size (1/2" OSB, etc.), R905. PLUMBING PLANS: 1. Show a vent for the kitchen sink, P3114. MECHANICAL PLANS: 1. Provide a Mechanical Plan showing heating facilities in all habitable rooms, R303.9. 2. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1. All other ducts outside of the thermal envelope require R-6 insulation. 3. Provide an equipment specification list including the (furnace and evaporative cooler) tonnage capacity, M1302.1. 4. Clarify the cooling capacity in accordance with M1401.3, M1601.1. The equipment schedule on the plans is not sized in accordance with Manual J calculations. ELECTRICAL PLANS: 1. Clarify if the sub panel "A" branch circuits #1- 6 are existing or replaced. 2. Show locations of each smoke alarm, R314. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.3.1. Provide notation if existing or proposed. 3. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315. 4. Protect all interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. 5. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. INTERNATIONAL ENERGY CONSERVATION CODE: 1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 (R-30 with conditions) and walls R=13. Show the maximum "U" factors of the windows on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |