Permit Number: T15CM04642
Parcel: 11714093A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T15CM04642
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2015 MICHAEL ST. PAUL ZONING REVIEW Approv-Cond Final approval of DP14-0013 and building approvals required.
08/12/2015 KEN BROUILLETTE FIRE REVIEW Reqs Change 1. Standpipes are required per 905.2.1
2. Stairway signs are required per 1022.9
3. Stairways need to terminiate correctly per 1022.3
4. Level III door P36 encroaches, please correct per 1005.7
Plan Reviewer is looking into 1029 as FD cannot ladder the building with only a 5 foot clearance
08/13/2015 JASON GREEN ENGINEERING REVIEW Reqs Change Approval of DP14-0013 is required prior to building plan approval. ELCERTs are required for the new building per the mapped 100-year floodplain.
08/19/2015 AROMERO4 WATER REVIEW Needs Review
08/20/2015 CPIERCE1 ADA REVIEW Needs Review
08/20/2015 CPIERCE1 HC SITE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2015 CPIERCE1 OUT TO CUSTOMER Completed