Permit Number: T15CM04568
Parcel: 115060840

Address:
101 E VENTURA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM04568
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The International Plumbing Code, 2012, is the controlling code for this structure, not the International Residential Code. Reference: Section 101.2, IPC 2012.
2. Provide fixture descriptions for all new plumbing fixtures. All fixtures shall be third-party listed. Reference: Section 402, IPC 2012 and Section 107.2.1, IBC 2012.
3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
4. Provide the number of drinking fountains that complies with the requirements of Section 1109.5.1, IBC 2012 and Section 410.2, IPC 2012.
5. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
6. Provide a partition between the urinal and the lavatory per Section 405.3.5, IPC 2012.
02/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/29/2016 ROBERT SHERRY WATER REVIEW Completed
07/21/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
07/21/2015 ELEIBOL1 ENGINEERING REVIEW Approved
07/21/2016 ARUIZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/21/2016 ARUIZ1 FIRE REVIEW Needs Review
07/21/2016 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
07/21/2016 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review