Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM04531
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Reqs Change | Provide a copy of the lst approved plot plan. |
| 07/06/2015 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | DATE: July 6, 2015 SUBJECT: Photovoltaic System TO: SolarCity Corporation REVIEWERS: Jason Green, CFM SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Site Plan for the installation of a photovoltaic system to an existing nonconforming structure at the above referenced property and does not recommend approval of the Site Plan at this time. The subject property is located within a mapped City of Tucson Flood Hazard Area as shown on the Flood Hazard Maps. Any improvements to the existing structure are considered a substantial improvement to an existing floodprone structure if the value of the new improvement is 50% or more than the assessed/appraised value of the existing structure. In order to help you permit the PV system we will need the following information from you. 1) Provide a cost estimate for the PV system installation to the existing structure showing fair market value of the material and labor. Please refer to the relative portions of the Handbook for Arizona Communities on Floodplain Management and the National Flood Insurance Program here; http://www.azwater.gov/azdwr/SurfaceWater/FloodManagement/documents/HandbookOct2000.pdf 2) Provide an assessed or appraised value of the existing single family. The assessed or appraised value is for the structure only (excluding land value). The assessed value can be provided by the latest assessment rolls of the county assessor prior to the improvements being started or from a licensed appraiser. 3) Provide a Floodplain Use Permit application with fees for review and approval on the next submittal. 4) Revise the site plan to accurately show the property dimensions. C17 and C18 dimensions should show the ARC not a straight line. GENERAL COMMENTS: Please provide a cost estimate and the assessed or appraised value of the structure along with a comment letter that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. If you have any questions, I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Planning & Development Services |
| 07/10/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Completed |