Permit Number: T15CM04430
Parcel: 14029003H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM04430
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
07/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/01/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1.Please provide compliance with the IECC for new interior lighting.
#2.Please designate panel for new lighting circuits on the lighting plan. Also locate the panel on the floor plan.
Ref: IBC sec. 107.2.1. NEC art. 408.4
07/01/2015 KEN BROUILLETTE FIRE REVIEW Approved
07/01/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: PLEASE PROVIDE A PLAN WITH THE TOTAL OFFICE SPACE (INCLUDING THE NEW SPACE) SHOWN (46,193 SF). INDICATE EXISTING PLUMBING FIXTURES (RESTROOMS, SERVICE SINKS, DRINKING FOUNTAINS). INDICATE EXITS AND TRAVEL DISTANCES.
2. SHEET S2.1; FOUNDATION PLAN: PLEASE LOCATE THE NEW HSS COLUMNS (3 THUS) ON THE PLAN.
3. STRUCTURAL CALCULATIONS: PLEASE PROVIDE CALCULATIONS FOR THE NEW COLUMN FOOTINGS (2 THUS).
4. STRUCTURAL CALCULATIONS: PLEASE PROVIDE A CALCULATION FOR THE EXISTING FOUNDATION UNDER THE NEW COLUMN (BETWEEN DOORS).
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/01/2015 ROBERT SHERRY WATER REVIEW Completed
07/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/01/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/07/2015 JASON GREEN ENGINEERING REVIEW Approved