Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM04395
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | BUILDING PLAN REVIEW COMMENTS Date: 8-17-15 Activity: T15CM04395 Address: 3208 N. Tucson Bvd Applicant: Joe Alitiem This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. Plans must be of sufficient clarity to indicate the location, nature and extent of the work proposed, 102.2.1. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval. 1. Please provide a fire-rated wall assembly on the north side of the structure or relocate the structure to accommodate the minimum five (5) foot fire separation distance from the property line, 406.3.2, Table 602, 705.2. If you have any questions please contact: Clayton Trevillyan, CBO 520.837.4913 Clayton.Trevillyan@tucsonaz.gov |
| 08/17/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/18/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following comments; #1. Provide a site plan showing the locations of all PV and service equipment include both services as shown on Plan Sheet 'PV4'. #2. The interconnection on the load side of the sub panel via the 40 amp PV circuit breaker is in violation of NEC art. 705.12D2. The conductors ( FEEDERS ) between the sub-panel and the Main Service panel would be considered an extension of the panel bus, therefore should rated as such (AMPACITY ). #3. The warning label ( 4 ) should also be applied to the inverters. NEC art.690.17. #4. Provide for a plaque / directory at each service location per NEC art.705.10 #5. Minimum font size for all plan documents is 3/32", per City of Tucson Plan Submittal Requirements. #6. Show wiring methods, ( conduit, conductor sizes and types ) between the shade structures and the buildings. #7. Provide light fixture schedule, details, layout, and full compliance with the Tucson outdoor lighting Code for the canopy lighting. Ref: IBC sec.107.2.1, NEC art. 300, 690, 705. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/24/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |