Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM04286
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. Vents running horizontally prior to rising at least 6" above the floor rim of the fixture they serve are still shown on sheets P-200B, P-403, P-404, P-506, and P-507. [Third comment: Comment not resolved. The flood rim of a floor drain or a floor sink is the finished floor level; the vents shall rise to 6" above the flood rim of the fixture they serve prior to running horizontally.] [Second comment: Four fixtures located in the main kitchen appear to have vents that do not rise to 6" above the flood rim of the fixture they serve prior to running horizontally.] [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] |
| 10/23/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Third comment: Provide the ventilation calculations that are the basis of the outside air quantities shown on the air balance data.] [Second comment: Comment not addressed.] [Initial comment: Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.] 2. Section 508.1, IMC 2012: "…The amount of make up air supplied to the building from all sources shall be approximately equal to the approximately equal to the amount of exhaust air for all exhaust systems in the building. ..." [Third comment: Correct the air balance chart to eliminate the extra KMU-2 unit and to add the outside air contributions on AC-3, AC-5, and AC-24.] [Second comment: Comment not addressed.] [Initial comment: Show that adequate make up air is being provided for the kitchen exhaust hoods and the ware washer, 1-110. Reference: Section 508.1 IMC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/29/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |