Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM04286
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | FIRE WILL HOLD APPROVAL OF THE COVERING OVER THE HEAVY TIMBER FRAMES THROUGHOUT UNTIL THE FIRE SPRINKLER SYSTEM PLANS ARE SUBMITTED. THE FIRE SPRINKLERS ARE REQUIRED PER IBC 1406.3. FIRE WILL WAIT FOR THE FIRE SPRINKLER DESIGNER TO PROVE THAT THE COVERINGS WILL WORK FOR SPRINKLER OPERATION. |
| 09/16/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/22/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Plaese address the following: #1. Last plan review comment #12 , "Feeder for panel '2LCBA' not tagged on the riser diagram, E-602". Please designate feeder type per wiring schedule. #2. Please provde for Tamper Resistant receptacles in living units as required per NEC art.406.13 |
| 09/23/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The automatic faucets for the lavatories located in public restrooms shall dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. [Initial comment: The automatic lavatory faucets shall provide a minimum flow period of 10-seconds. Reference: Section 606.4, ICC/ANSI A117.1-03.] 2. Four fixtures located in the main kitchen appear to have vents that do not rise to 6" above the flood rim of the fixture they serve prior to running horizontally. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] 3. Scuppers are neither vertical conductors (Table 1106.2) nor horizontal pipes running full (Table 1106.3) and cannot be sized as such. Scuppers are weirs (generally rectangular) and are hydraulically calculated to limit the ponding on the roof. To limit the ponding on a 5300 square-foot roof to 2" would require a weir that is 19.8" wide. Provide the calculations used to determine the size of the scuppers. [Initial comment: Provide the dimensions of the overflow scuppers and the hydraulic calculations used to determine the size of the scuppers. Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012 and Sections 1611.1 and 1611.3, IBC 2012.] 4. Revise the 2-PSIG natural gas schematic (P-501) to show the correct gas input loads for the rooftop units, the kitchen make-up units and the salamander (see sheets M-002 and FS-1.3). [Initial comment: Revise the 2-PSIG natural gas schematic (P-501) to show all of the loads (e.g. include the piping to the rooftop units) and the developed lengths of the piping from each load to the meter. Provide gas pipe sizing calculations demonstrating conformance to Section 402.1 and 402.3, IFGC 2012. Reference: Section 107.2.1, IBC 2012.] 5. The discharge of the elevator sump pump is shown connecting to a 3" branch of the building drain. With a minimum discharge of 50 GPM, a 4" drain line is required per Sections 709.3 and 710.1, IPC 2012. In addition, verify that the Regional Wastewater Reclamation Department (520-724-6200) will allow the elevator sump to discharge to sanitary waste. |
| 09/30/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: In the COMcheck Envelope Compliance Certificate, the high efficiency HVAC option was selected as the additional efficiency package requirement to comply with Section C406, IECC 2012. In the Interior Lighting and Mechanical Compliance Certificates, however, reduced indoor lighting power option is noted as the way to comply with the additional efficiency package requirement. Coordinate the approach to be used to comply with Section C406, IECC 2012.] 2. Comment not addressed. [Initial comment: Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (e.g. include the doors and the multiple window types). Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1 and C303.1.3, IECC 2012, as amended by the City of Tucson.] 3. Comment not addressed. [Initial comment: The NFRC certification numbers (CPD#) have not been included in this submittal. Factory-manufactured windows are required to have certificates attesting to their compliance to NFRC Standards 100 and 200 and can be provided by the manufacturer or found at www.nfrc.org. For site assembled commercial products, the NFRC component modeling approach program enables commercial window manufacturers to produce bid reports to prove energy performance prior to being awarded a job and provide finalized label certificates once the product has been installed. Fenestration performance reports based on AAMA 507 are based on energy simulations only (no actual testing) and are not acceptable.] 4. Comment not addressed. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.] 5. Comment not addressed. [Initial comment: Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.] 6. Comment not addressed. [Initial comment: Verify that the proposed Type I hood is equipped to automatically start the hood exhaust fan when cooking operations commence. Reference: Section 507.2.1.1, IMC 2012.] 7. Comment not addressed. [Initial comment: Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.] 8. Comment not addressed. [Initial comment: Show that the latent and sensible loads from the ware washer, 3-038, are included in the HVAC design. Reference: Section 507.2.2, IMC 2012.] 9. Comment not addressed. [Initial comment: Show that adequate make up air is being provided for the kitchen exhaust hoods and the ware washer, 1-110. Reference: Section 508.1 IMC 2012.] 10. Comment not addressed. [Initial comment: Clarify the reason for not utilizing fire dampers in the transfer ducts penetrating rated partitions when the associated ducted HVAC system is shown with fire dampers where the duct penetrates the same partitions (e.g. AC-2, AC-9, AC-11, and AC-19). Reference: Section 107.2.1, IBC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/09/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 10/09/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |