Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM04248
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. State that the specified lavatory faucet will be set to deliver a maximum of 0.25 gallons per cycle and will operate for at least 10 seconds per cycle. 2. Clarify how tempered water (i.e. 90-110 degrees Fahrenheit) will be delivered to the lavatory faucet. 3. Revise the water piping (e.g. the non-existant HW), sanitary and vent piping to reflect the field conditions. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/09/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |