Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM04248
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/22/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/05/2015 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | A special Exception process is required for this non-chartered financial Use. |
10/05/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/05/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide circuit designations for new receptacles and a complete panel schedule and panel location on the plans. Ref; IBC sec. 107.2.1 NEC art. 408. |
10/05/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
10/05/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET C1; PROJECT DATA: THE OCCUPANT LOAD IS LISTED AS 20, WHICH REQUIRES TWO ACCESSIBLE RESTROOMS PER THE IBC SECTION 2902.2. PLEASE REVISE. 2. GENERAL: PLEASE PROVIDE A PROJECT VALUATION. |
10/05/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/05/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/05/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |