Permit Number: T15CM04129
Parcel: 13204007A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM04129
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
06/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following:
#1. Remove the 20/1 on circuit #17 panel schedule for " KA ". Include load calc's. Plan Sheet E0.1
#2. Feeder for new 3 phase panel " DA " should be 3-#4 and 1 # 10. Plan Sheet E 1.1.
#3. Provide a complete one line diagram, include fault current, total load.
#4. Verify voltage for new luminaires fed by existing circuit.
#5. Verify circuit breaker ampacity for the new ac unit.
REF; IBC sec. 107.2.1. NEC art. 300, 408.
06/18/2015 JASON GREEN ENGINEERING REVIEW Approved
06/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/18/2015 ROBERT SHERRY WATER REVIEW Completed
06/18/2015 MARTIN BROWN FIRE REVIEW Approved
06/23/2015 AROMERO4 BUILDING-COMMERCIAL REVIEW Needs Review
06/23/2015 AROMERO4 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review