Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM04129
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/18/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/18/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following: #1. Remove the 20/1 on circuit #17 panel schedule for " KA ". Include load calc's. Plan Sheet E0.1 #2. Feeder for new 3 phase panel " DA " should be 3-#4 and 1 # 10. Plan Sheet E 1.1. #3. Provide a complete one line diagram, include fault current, total load. #4. Verify voltage for new luminaires fed by existing circuit. #5. Verify circuit breaker ampacity for the new ac unit. REF; IBC sec. 107.2.1. NEC art. 300, 408. |
| 06/18/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 06/18/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/18/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/18/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/23/2015 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/23/2015 | AROMERO4 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |