Permit Number: T15CM04119
Parcel: 116273140

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM04119
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2015 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: June 22, 2015
SUBJECT: Photovoltaic System
TO: SolarCity Corporation
REVIEWERS: Jason Green, CFM


SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the Site Plan for the installation of a photovoltaic system and does not recommend approval of the Site Plan at this time.

1) Revise the site plan to accurately show the structure within the property dimensions.


If you have any questions, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning & Development Services
06/24/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T15CM04119
3232 W. Bird Haven place
Residential (1st Review)

TRANSMITTAL DATE: June 24, 2015

The solar plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

1. House size and orientation on the parcel is not correct.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/26/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed