Permit Number: T15CM03998
Parcel: 141185900

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM03998
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/30/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise detail 117 to show all of the clearance dimensions to scale. [Initial comment: Clarify how the low-intensity infra-red heater is to be mounted in the patio area given the minimum clearances shown in detail 107/M2.0 (the roof is combustible). Reference: Section 304.1, IMC 2012.]
07/30/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a direct connection for hand sink 508.1. [Initial comment: Clarify the reason for using an indirect waste connection for the hand sinks (66 (2), 66.1, 66.2, 67, and 508.1). Reference: Section 802.1, IPC 2012.]
07/31/2015 AROMERO4 WATER REVIEW Needs Review
07/31/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/31/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/31/2015 AROMERO4 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2015 AROMERO4 OUT TO CUSTOMER Completed