Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM03998
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/30/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise detail 117 to show all of the clearance dimensions to scale. [Initial comment: Clarify how the low-intensity infra-red heater is to be mounted in the patio area given the minimum clearances shown in detail 107/M2.0 (the roof is combustible). Reference: Section 304.1, IMC 2012.] |
| 07/30/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a direct connection for hand sink 508.1. [Initial comment: Clarify the reason for using an indirect waste connection for the hand sinks (66 (2), 66.1, 66.2, 67, and 508.1). Reference: Section 802.1, IPC 2012.] |
| 07/31/2015 | AROMERO4 | WATER | REVIEW | Needs Review | |
| 07/31/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/31/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 07/31/2015 | AROMERO4 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/31/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |