Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM03998
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 06/22/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Native @ Old Vail Plaza T15CM3998 Building Plan (1st Review) TRANSMITTAL DATE: June 22, 2015 1. The building plan have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. It appears that the plans match development package DP14-0248 but cannot be approved until the development package is approved. 3. Zoning will not approve until all other PDSD agencies have approved the building plan. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 06/24/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Correct the calculations of the required number of plumbing fixtures. The number of required fixtures shown in Table 2902.1, IBC 2012 is based upon the minimum fixtures required for each person or fraction of the number of persons. With a total population of 239, the number of water closets and lavatories shall be based on 120 males and 120 females. Since fractional fixtures cannot be installed, fractional numbers for fixtures shall also be rounded up to the next whole number. Correct the number of provided fixtures to coordinate with the number of fixtures shown on the plans. Reference: footnote (a), Table 2902.1, IBC 2012. 2. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012. 3. Provide a site drawing showing the location of the proposed gravity grease interceptor, the size, route, and slope of the building sewer, the location of all cleanouts in the building sewer, and the location of the connection of the building sewer to the public sewer. Reference: Section 107.2.1, IBC 2012. 4. Appliances (e.g. soda dispensers, ice makers, easiwash, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 5. Clarify the reason for using an indirect waste connection for the hand sinks (66 (2), 66.1, 66.2, 67, and 508.1). Reference: Section 802.1, IPC 2012. 6. Provide secondary (overflow) roof drainage; the "overflow openings" in the collector boxes do not provide for secondary roof drainage. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012. 7. Show the installation of a roof scupper (along with provision for secondary roof drainage) for the high roof on sheet A6.1. Reference: Section 107.2.1, IBC 2012. |
| 06/24/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Clarify the size of the proposed water meter and the associated reduced pressure backflow preventer. On sheet P1.1 they are both 2" but on sheet P3.0 both are only 1-1/2". Reference: Section 107.2.1, IBC 2012. |
| 06/25/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with IECC for interior lighting. |
| 06/25/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the balancing information for AC-2. On sheet M1.0, two diffusers are labeled at 300 CFM and the remaining label calls for eight diffusers at 400 CFM each but there are only eight diffusers on AC-2. Reference: Section 107.2.1, IBC 2012. 2. Clarify how the low-intensity infra-red heater is to be mounted in the patio area given the minimum clearances shown in detail 107/M2.0 (the roof is combustible). Reference: Section 304.1, IMC 2012. 3. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 4. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. 5. Show how the "Additional Efficiency Package Requirements" noted in COMcheck (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012. |
| 06/26/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/15/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | BUILDING PLAN REVIEW COMMENTS Date: 7-17-15 Activity: T15CM03998 Address: 10255 E. Old Vail Rd Applicant: Diana Flynn This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval. Sheet T1.1 1. Please correct the value shown for half the diagonal distance between exits shown on the exit plan. This value should be 49.5', 107.2.1. 2. Please correct the value specified for the minimum number of plumbing fixtures required for each sex. The number required and the number provided exceed the values indicated, 2902.1. Sheet AS1.1 3. A minimum of three (3) accessible parking spaces are required for the number of parking spaces provided, 1106.1. Sheet A6.1 4. Specify how drainage will occur from the upper roof and the method of emergency overflow from drains or scuppers, 1503.4. If you have any questions please contact: Clayton Trevillyan, CBO 520.837.4913 Clayton.Trevillyan@tucsonaz.gov |
| 07/17/2015 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |