07/08/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM03991

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. Provide details for floor joist (keynote B) connections to supporting structure, R106.1.1. Show untreated wood framing with a minimum 8" clearance above the ground, R317.1 item 2, or show as pressure treated. Also, include R=13 floor insulation, N1102.1
2. Provide details for beam (keynote L) connections to support posts and floor structure being supported, R106.1.1.

PLUMBING PLANS:

1. Show the water heater with a listed pan and ¾" drain line to a waste receptor or to the building exterior 6" above grade, P2801.5.
2. Show a pressure and temperature relief valve at the water heater. Note a metallic T&P line terminating at the exterior 6 inches above grade facing down, P2803.6.1.
3. Provide a water hammer arrester for quick-closing valves serving the clothes washer, P2903.5.

MECHANICAL PLANS:

1. Show any changes to the mechanical systems, R106.1.1.
2. Verify heating facilities in all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Show locations of each smoke alarm, R314. Notate that all smoke alarms must be interconnected with a power source from the building wiring, and be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms be in compliance. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke alarms, R314.2.
2. Show a smoke alarm on each side of the bedroom doors in the immediate vicinity. Show a smoke alarm on each story of the dwelling, R314.3.3.
3. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3404.12.
4. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.12 & E3706.2.